GSU Transformer Upgrade – Tank
Hot Spot - Summary
Significant localized tank cover
flange heating had been observed by infrared scan on a 185 MVA GSU
transformer, compromising the aimed upgrading (by 23%) of the name
plate MVA rating.
The enhanced oil cooling could not cope with the
localized tank hot spot. The simulation provided a good match with
the measured tank temperatures.
Additional studies allowed the
verification of alternative designs for the LV busbars enclosure.
Thanks to the simulations the proper solution was identified!
Description